Psychrometric chart dew point calculator
Plot any air condition on a live psychrometric chart. Enter dry bulb temperature, relative humidity and pressure, then drag the point: the dew point, wet bulb, humidity ratio, enthalpy and specific volume update as you go.
Plot your air state
Move a slider or type a value. Results and the chart update as you go.
How psychrometric chart dew point calculator works?
To find dew point on the psychrometric chart, the calculator plots your dry bulb temperature and relative humidity (RH), then moves left at constant humidity ratio to the saturation curve. It returns dew point, wet bulb, humidity ratio, enthalpy and specific volume at your air pressure.
- Find your dry bulb temperature on the horizontal axis and go up to your relative humidity curve. That point is your air.
- Move horizontally to the left, at constant humidity ratio, until you hit the 100% saturation curve.
- Read straight down to the temperature axis. That temperature is the dew point.
- The calculator does the same, and adds wet bulb, humidity ratio, enthalpy and specific volume.
Psychrometric chart dew point calculator formula
The psychrometric chart follows the ASHRAE Handbook equations: humidity ratio W = 0.622 × e ÷ (p − e), enthalpy h = 1.006·T + W·(2501 + 1.86·T) kJ/kg and specific volume v = 0.287 × (T + 273.15) × (1 + 1.608·W) ÷ p. The dew point is the saturation temperature at constant W.
- T dry bulb temperature, °C
- e vapour pressure, hPa
- p air pressure, hPa (or kPa in v)
- W humidity ratio, kg/kg (× 1000 for g/kg, × 7000 for grains/lb)
- h enthalpy, kJ/kg (1 kJ/kg = 0.43 Btu/lb)
- v specific volume, m³/kg
Psychrometric chart dew point calculator conversion chart
Values at sea-level pressure (1013.25 hPa), computed with the same equations as the calculator.
| Air state | Dew point (°C) | Wet bulb (°C) | Humidity ratio (g/kg) | Enthalpy (kJ/kg) |
|---|---|---|---|---|
| 20 °C, 50% | 9.3 | 13.9 | 7.26 | 38.5 |
| 22 °C, 45% | 9.5 | 14.8 | 7.39 | 40.9 |
| 25 °C, 50% | 13.9 | 18.0 | 9.88 | 50.3 |
| 25 °C, 70% | 19.1 | 21.0 | 13.92 | 60.6 |
| 30 °C, 60% | 21.4 | 23.9 | 16.04 | 71.2 |
| 35 °C, 40% | 19.4 | 24.1 | 14.13 | 71.5 |
How to find dew point on a psychrometric chart
- Find the dry bulb temperature on the bottom axis and go up.
- Stop where you meet the relative humidity curve. That is the state point.
- Move horizontally left to the 100% curve.
- Read the dew point on the saturation curve.
Example: 25 °C and 50% RH gives a state point at 9.9 g/kg and a dew point of 13.9 °C.
Psychrometric processes and the dew point
| Process | Direction on the chart | Dew point |
|---|---|---|
| Sensible heating | Right | Unchanged |
| Sensible cooling (above dew point) | Left | Unchanged |
| Cooling and dehumidifying | Left, then down the saturation curve | Falls |
| Evaporative cooling | Up and left along a wet bulb line | Rises |
| Steam humidifying | Almost straight up | Rises |
Psychrometric formulas
The chart is drawn from a handful of ASHRAE equations: vapour pressure e = RH × es(T), humidity ratio W = 0.622 × e ÷ (p − e), enthalpy h = 1.006·T + W·(2501 + 1.86·T) kJ/kg and specific volume v = 0.287·(T + 273.15)·(1 + 1.608·W) ÷ p.
Psychrometric properties at a glance
| Property | Symbol | Unit | Line shape on chart |
|---|---|---|---|
| Dry bulb | T | °C | Vertical |
| Humidity ratio | W | g/kg | Horizontal |
| Dew point | Td | °C | Horizontal |
| Relative humidity | φ | % | Curves |
| Wet bulb | Tw | °C | Diagonal |
| Enthalpy | h | kJ/kg | Diagonal (near wet bulb) |
| Specific volume | v | m³/kg | Steep diagonal |
Common HVAC design points
| Condition | Dry bulb | RH | Dew point |
|---|---|---|---|
| Summer office | 24 °C | 50% | 12.9 °C |
| Winter office | 21 °C | 35% | 5.0 °C |
| Cooling coil leaving air | 13 °C | 95% | 12.2 °C |
| Data centre (ASHRAE) | 24 °C | 45% | 11.3 °C |
| Museum storage | 20 °C | 50% | 9.3 °C |
Psychrometric chart dew point calculator FAQs
How do you find the dew point on a psychrometric chart?
Plot the state point, then move horizontally to the left at constant humidity ratio until you hit the saturation (100% RH) curve. Read the temperature there: that is the dew point.
Where is the dew point scale on a psychrometric chart?
On the saturation curve on the left edge, which doubles as the wet bulb and dew point scale. Some charts also print a dew point scale on the right-hand side next to the humidity ratio axis.
Why are dew point lines horizontal?
Dew point depends only on the amount of water vapour, which is the humidity ratio on the vertical axis. Constant moisture means constant dew point, so the lines are horizontal.
What's the difference between wet bulb and dew point on the chart?
Wet bulb lines slope diagonally down to the right; dew point lines are horizontal. Both are read on the saturation curve, and they meet only at 100% RH.
What happens when air is cooled below its dew point on the chart?
The process line moves left until it reaches the saturation curve, then follows the curve down. Water condenses, which is how cooling coils dehumidify air.
Does a psychrometric chart depend on altitude?
Yes. Standard charts are for sea-level pressure. At high altitude use a chart (or calculator) for your local pressure.
What two values do I need to use a psychrometric chart?
Any two independent properties, such as dry bulb and RH, dry bulb and wet bulb, or dry bulb and dew point.
What formulas are behind a psychrometric chart?
The formulas behind a psychrometric chart are W = 0.622e/(p − e), h = 1.006T + W(2501 + 1.86T) and v = 0.287(T + 273.15)(1 + 1.608W)/p, from the ASHRAE Handbook of Fundamentals.
What is the enthalpy of air at 25 °C and 50% RH?
Air at 25 °C (77 °F) and 50% relative humidity has an enthalpy of about 50 kJ/kg.
Who publishes the psychrometric chart used in HVAC?
ASHRAE (the American Society of Heating, Refrigerating and Air-Conditioning Engineers) publishes the standard psychrometric charts used in HVAC design.