Dew point calculator wet bulb dry bulb

Enter the dry bulb and wet bulb readings from a sling or aspirated psychrometer and your air pressure. The calculator returns the dew point, relative humidity, wet bulb depression and vapour pressure using the psychrometer equation with a pressure correction.

Dew point from DB and WB

Move a slider or type a value. Results and the chart update as you go.

°C
°C
hPa

How dew point calculator wet bulb dry bulb works?

To calculate dew point from wet bulb and dry bulb temperatures, the calculator applies the psychrometer equation to find the actual vapour pressure, then solves for the dew point. It corrects for air pressure in hectopascals (hPa), so readings from high-altitude sites stay accurate.

  1. It takes the wet bulb depression: dry bulb minus wet bulb. The bigger the gap, the drier the air.
  2. It applies the psychrometer equation: e = es(Tw) − 0.00066 × (1 + 0.00115·Tw) × p × (T − Tw).
  3. That gives the actual vapour pressure, e. The dew point is the temperature where saturation pressure equals e.
  4. Relative humidity is e divided by the saturation pressure at the dry bulb temperature.

Dew point calculator wet bulb dry bulb formula

The psychrometer equation is e = es(Tw) − A × p × (T − Tw), with A = 6.6 × 10⁻⁴ × (1 + 0.00115 × Tw) per °C for a ventilated instrument. Ernst Ferdinand August named and developed the psychrometer in 1825; the equation still carries his method. The dew point is the temperature at which es equals e.

Dew point calculator wet bulb dry bulb conversion chart

Dry bulb on the left, wet bulb depression (dry bulb minus wet bulb) across the top, at sea-level pressure. Values are dew points in °C.

Dew point from wet bulb depression: Dew point (°C) by dry bulb temperature and wet bulb depression, 1013 hPa
Dry bulb−1 °C−2 °C−4 °C−6 °C−8 °C−10 °C
10 °C861−5−16—
15 °C131283−4−14
20 °C181713105−1
25 °C24221916127
30 °C292725221815
35 °C343330272421
40 °C393835333027

Wet bulb, dry bulb and dew point compared

Temperature How it’s measured What it represents
Dry bulb Ordinary thermometer in shade Air temperature
Wet bulb Thermometer with a wet wick, ventilated Lowest temperature reachable by evaporation
Dew point Chilled mirror or calculated Temperature at which vapour condenses

The order never changes: dew point ≤ wet bulb ≤ dry bulb.

How to read a sling psychrometer

  1. Soak the wick in distilled water.
  2. Whirl the psychrometer for 60–90 seconds at arm’s length, in the shade.
  3. Read the wet bulb first (it rises quickly once you stop), then the dry bulb.
  4. Repeat until two wet bulb readings agree within 0.2 °C.
  5. Enter both temperatures and your air pressure above.

The psychrometer equation, step by step

e = es(Tw) − A × p × (T − Tw), with A = 6.6 × 10⁻⁴ × (1 + 0.00115 × Tw) for a well-ventilated instrument and p in hPa. Example at sea level, T = 30 °C and Tw = 22 °C: es(22) = 26.44 hPa, the correction is 5.49 hPa, so e = 20.96 hPa and the dew point is 18.2 °C with RH 49%.

Dew point from wet bulb depression (sea level)

Dry bulb Depression 2 °C 4 °C 6 °C 8 °C 10 °C
10 °C 6.0 1.2 −5.4 −16.4 —
15 °C 11.6 7.6 2.7 −3.8 −14.5
20 °C 16.9 13.5 9.5 4.8 −1.4
25 °C 22.2 19.1 15.7 11.9 7.3
30 °C 27.4 24.6 21.5 18.2 14.5
35 °C 32.5 29.9 27.1 24.2 21.0
40 °C 37.6 35.1 32.5 29.8 26.9

Psychrometer vs electronic hygrometer

Sling psychrometer Electronic hygrometer
Accuracy ±2–5% RH if used well ±1.5–3% RH
Below 0 °C Difficult (ice bulb) Works
Calibration Only thermometers Needs periodic calibration
Cost Low Low to high
Best for Field checks, coatings, HVAC audits Continuous monitoring

Dew point calculator wet bulb dry bulb FAQs

How do you calculate dew point from wet bulb and dry bulb?

Use the psychrometer equation to find the actual vapour pressure: e = es(Tw) − A·p·(T − Tw), with A ≈ 6.6 × 10⁻⁴ per °C for a ventilated psychrometer. Then find the temperature where saturation pressure equals e: that's the dew point.

Is wet bulb temperature the same as dew point?

No. The wet bulb is always between the dew point and the dry bulb. All three are equal only at 100% relative humidity.

What is wet bulb depression?

The difference between the dry bulb and wet bulb readings. A big depression means dry air; zero depression means saturated air.

Does altitude affect wet bulb calculations?

Yes. Lower air pressure reduces the psychrometer correction, so the same readings give a slightly higher dew point at altitude. Enter your station pressure for accuracy.

How do I use a sling psychrometer correctly?

Wet the wick with clean water, whirl the instrument for 1–2 minutes in the shade, read the wet bulb, whirl again, and repeat until the wet bulb stops falling. Read the dry bulb at the same time.

Why is wet bulb temperature important for heat stress?

The wet bulb reflects how well sweat can cool the body. Sustained wet bulb temperatures above about 31–35 °C are dangerous even for healthy people at rest.

What is the wet bulb at 30 °C and 50% RH?

About 22.1 °C at sea level, with a dew point of 18.4 °C.

Can the wet bulb be below freezing?

Yes. If the wick freezes, you're measuring an ice bulb, which needs a different coefficient. Below 0 °C most technicians switch to an electronic hygrometer.

What is the wet bulb dry bulb dew point formula?

The formula is e = es(Tw) − A × p × (T − Tw), followed by solving es(Td) = e for the dew point Td.

Who invented the psychrometer?

Ernst Ferdinand August, a German physicist, named and developed the psychrometer in 1825.

What is the dew point with a 30 °C dry bulb and 25 °C wet bulb?

A 30 °C (86 °F) dry bulb and 25 °C (77 °F) wet bulb at sea level give a dew point of 23 °C (74 °F).