Apparatus dew point temperature calculator
Enter the air conditions entering and leaving a cooling coil. The calculator extends the coil process line to the saturation curve to find the apparatus dew point (ADP), then gives the bypass factor, contact factor, sensible heat ratio and moisture removed.
Find the apparatus dew point of a coil
Move a slider or type a value. Results and the chart update as you go.
How apparatus dew point temperature calculator works?
To calculate apparatus dew point (ADP), the calculator plots the entering and leaving air on the psychrometric chart, draws the coil process line through them and extends it to the saturation curve. It returns the ADP, bypass factor (BF), contact factor and sensible heat ratio (SHR).
- It converts the entering and leaving dry bulb and RH into humidity ratios.
- It draws a straight process line through the two states on the psychrometric chart.
- It extends the line until it meets the saturation (100% RH) curve: that temperature is the apparatus dew point.
- Bypass factor = (leaving − ADP) ÷ (entering − ADP); contact factor = 1 − bypass factor.
Apparatus dew point temperature calculator formula
The bypass factor is BF = (T₂ − ADP) ÷ (T₁ − ADP); the contact factor is CF = 1 − BF. Rearranged, ADP = (T₂ − BF × T₁) ÷ (1 − BF). The ASHRAE Handbook uses the same coil model for cooling and dehumidifying coils.
- T₁, T₂ entering and leaving dry bulb, °C
- W₁, W₂ entering and leaving humidity ratio, g/kg
- ADP apparatus dew point, °C
- BF bypass factor (0–1)
- SHR sensible heat ratio = sensible ÷ total heat
Apparatus dew point temperature calculator conversion chart
Leaving dry bulb for a coil with entering air at 27 °C and an apparatus dew point of 10 °C.
| Bypass factor | Contact factor | Leaving dry bulb | Leaving dew point |
|---|---|---|---|
| 0.05 | 0.95 | 10.8 °C | 10.3 °C |
| 0.10 | 0.90 | 11.7 °C | 10.7 °C |
| 0.15 | 0.85 | 12.6 °C | 11.0 °C |
| 0.20 | 0.80 | 13.4 °C | 11.3 °C |
| 0.30 | 0.70 | 15.1 °C | 11.9 °C |
| 0.40 | 0.60 | 16.8 °C | 12.5 °C |
Bypass factor and leaving air
Leaving air is a mix of fully treated air at the ADP and bypassed entering air. The bypass factor sets the proportions.
ADP formulas
The same relationship, rearranged, gives ADP from measured temperatures when the bypass factor is known.
ADP vs dew point vs coil surface temperature
| Term | Meaning |
|---|---|
| Apparatus dew point | Effective coil temperature from the air-side process line |
| Leaving air dew point | Moisture content of the air after the coil |
| Coil surface temperature | Actual fin and tube temperature, varies across the coil |
| Chilled water supply | Usually 2–5 °C below ADP |
Apparatus dew point temperature calculator FAQs
What is apparatus dew point?
The effective surface temperature of a cooling coil: the point where the coil's process line meets the saturation curve on a psychrometric chart.
How do you calculate apparatus dew point?
Plot entering and leaving air on the psychrometric chart, draw a line through them and extend it to the saturation curve. The calculator solves this numerically.
What is bypass factor?
The fraction of air that effectively passes the coil without touching it. BF = (leaving − ADP) ÷ (entering − ADP).
What is a typical bypass factor?
About 0.05–0.3 for comfort cooling coils. More rows and lower face velocity give lower bypass factors.
Is apparatus dew point the same as coil temperature?
No, close but not equal. ADP is an effective value from the air side; the actual fin and tube temperatures vary across the coil.
What if the line never reaches saturation?
The leaving state is inconsistent with a single coil process (for example more moisture removed than cooling allows). Check the measurements.
What is the apparatus dew point formula?
The apparatus dew point formula is ADP = (T₂ − BF × T₁) ÷ (1 − BF), from the bypass factor BF = (T₂ − ADP) ÷ (T₁ − ADP).
What is a typical apparatus dew point for comfort cooling?
A typical apparatus dew point for comfort cooling is 7–13 °C (45–55 °F).
What sensible heat ratio does a coil have?
A comfort cooling coil typically has a sensible heat ratio of 0.65–0.85; lower values mean more moisture removal.