SF6 dew point calculator
Gas-insulated switchgear needs very dry SF₆. Enter the moisture reading and filling pressure to get the dew point at atmospheric pressure, the dew point at filling pressure and the moisture by weight.
SF₆ moisture conversion
Move a slider or type a value. Results and the chart update as you go.
How SF6 dew point calculator works?
To convert sulfur hexafluoride (SF₆) moisture, the calculator takes ppm by volume, finds the dew point at atmospheric pressure and at your filling pressure, and converts to ppm by weight with SF₆'s molar mass of 146.06 g/mol.
- It takes the water content in ppm by volume, which doesn't change with pressure.
- It finds the frost or dew point at atmospheric pressure, which is how most portable SF₆ analysers report.
- It finds the dew point at your filling pressure: the temperature at which water would actually condense inside the equipment.
- It converts to ppm by weight with SF₆'s molar mass of 146.06 g/mol: ppm(w) = ppm(v) × 18.015 ÷ 146.06.
SF6 dew point calculator formula
The SF₆ moisture formulas are f·es(Td) = x × p and ppmw = ppmv × 18.015 ÷ 146.06. John Dalton's law of partial pressures (1801) underpins the method: water vapour keeps its own share of the total pressure, so its partial pressure is the mole fraction times the absolute pressure.
- ppmv water by volume (molecules)
- ppmw water by weight, about 0.123 × ppmv
- p pressure, bar a (1 bar = 0.1 MPa = 14.5 psi)
- Td dew or frost point, °C
SF6 dew point calculator conversion chart
Dew points for common SF₆ moisture levels at atmospheric pressure and at typical filling pressures. Frost point below 0 °C.
| ppm(v) | ppm(w) | Dew point at 1 atm | At 5 bar a | At 7 bar a |
|---|---|---|---|---|
| 25 | 3.1 | −53.6 °C | −40.4 °C | −37.5 °C |
| 50 | 6.2 | −48.0 °C | −34.2 °C | −31.1 °C |
| 100 | 12.3 | −42.1 °C | −27.5 °C | −24.3 °C |
| 200 | 24.7 | −35.9 °C | −20.6 °C | −17.1 °C |
| 300 | 37.0 | −32.2 °C | −16.3 °C | −12.7 °C |
| 500 | 61.7 | −27.3 °C | −10.7 °C | −6.9 °C |
| 1,000 | 123.3 | −20.2 °C | −2.7 °C | 1.5 °C |
| 2,000 | 246.7 | −12.8 °C | 6.7 °C | 11.6 °C |
Why moisture in SF₆ matters
Water in SF₆ reduces insulator surface strength if it condenses, and reacts with arc decomposition products to form corrosive acids. Dry gas keeps breakers and GIS reliable.
Measuring SF₆ moisture
- Connect a moisture analyser rated for SF₆ to the compartment’s test port.
- Purge the sample line until the reading is stable.
- Record moisture, pressure and temperature together.
- Recover the sample gas rather than venting it (SF₆ is a very potent greenhouse gas).
Transformers and other SF₆ equipment
Gas-insulated transformers and instrument transformers use the same conversion. Always quote a dew point with its pressure: −30 °C at 1 atm is a much drier gas than −30 °C at 6 bar.
SF₆ moisture conversion table
| ppmv | ppmw | Dew point at 1 atm | At 5 bar a | At 7 bar a |
|---|---|---|---|---|
| 25 | 3.1 | −53.6 °C | −40.4 °C | −37.5 °C |
| 50 | 6.2 | −48.0 °C | −34.2 °C | −31.1 °C |
| 100 | 12.3 | −42.1 °C | −27.5 °C | −24.3 °C |
| 200 | 24.7 | −35.9 °C | −20.6 °C | −17.1 °C |
| 300 | 37.0 | −32.2 °C | −16.3 °C | −12.7 °C |
| 500 | 61.7 | −27.3 °C | −10.7 °C | −6.9 °C |
| 1,000 | 123.3 | −20.2 °C | −2.7 °C | 1.5 °C |
| 2,000 | 246.7 | −12.8 °C | 6.7 °C | 11.6 °C |
Ways to express SF₆ moisture compared
| Unit | Depends on pressure? | Notes |
|---|---|---|
| ppmv | No | Most common in IEC standards |
| ppmw | No | About 8 times smaller than ppmv |
| Dew point at 1 atm | No (fixed reference) | What portable analysers show |
| Dew point at filling pressure | Yes | What matters for condensation inside |
SF6 dew point calculator FAQs
How do you convert SF₆ ppmv to ppmw?
Multiply by 18.015 and divide by 146.06 (molar mass of SF₆). 200 ppmv is about 24.7 ppmw.
Why is SF₆ ppmw so much lower than ppmv?
SF₆ molecules are about eight times heavier than water molecules, so the same number of water molecules is a much smaller share of the mass.
What is the SF₆ dew point limit?
IEC 60376 (new gas) and IEC 60480 (re-used gas) set maximum moisture limits that depend on the equipment's pressure, and manufacturers set their own values. Check the current edition and the equipment manual, and compare at the same reference pressure.
Why does dew point at filling pressure matter?
It's the temperature at which water would actually condense on insulators inside the equipment, and it must stay below the lowest ambient temperature.
Does SF₆ moisture change with temperature?
Yes. The ppmv inside the compartment can rise on hot days as adsorbents and surfaces release water. Measure at a stable temperature and note it.
How is SF₆ moisture measured?
With chilled-mirror or capacitive analysers designed for SF₆, ideally with gas recovery so none is vented.
What happens if SF₆ is too wet?
Water can condense on insulators and, with arc by-products, form corrosive HF and other acids. The gas must be dried with a gas-handling cart.
What is the formula to convert SF₆ ppmv to ppmw?
The formula is ppmw = ppmv × 18.015 ÷ 146.06, which equals ppmv × 0.1233.
What is 200 ppmv in SF₆ as a dew point?
200 ppmv of water in SF₆ is a frost point of −36 °C at 1 atm and −19 °C at 6 bar a.
What does IEC 60480 cover?
IEC 60480 gives guidance on checking and treating SF₆ taken out of electrical equipment, including moisture limits for re-use.