Dew point calculator roof

Choose your roof type, set indoor and outdoor conditions and the insulation R-value. The calculator shows the temperature through every layer, the deck temperature and whether moist indoor air would condense anywhere in the roof.

Check your roof for condensation

Move a slider or type a value. Results and the chart update as you go.

°C
%
°C
m²K/W

How dew point calculator roof works?

To find the dew point in a roof, the calculator builds the layers for a warm flat roof, cold flat roof or pitched roof, shares the temperature drop by R-value and compares each layer with the indoor dew point. Warm roofs keep the deck above the dew point; cold roofs don't.

  1. It calculates the indoor dew point from room temperature and humidity.
  2. It builds the layers for your roof type: a warm flat roof has insulation above the deck; a cold flat roof and a loft have it at ceiling level.
  3. It shares the indoor-to-outdoor temperature drop across the layers in proportion to their R-values, using the upward heat-flow surface resistance of 0.10 m²K/W inside.
  4. It flags the first layer colder than the indoor dew point. That's where moist air leaking into the roof would condense.

Dew point calculator roof formula

Layer temperatures follow Tx = Tin − (Tin − Tout) × ΣR to x ÷ ΣR total, with an inside surface resistance of 0.10 m²K/W for upward heat flow and 0.04 m²K/W outside. The deck is safe when T deck > Td indoor.

Dew point calculator roof conversion chart

Indoor dew point at 20 °C (68 °F) for common humidity levels, and the deck temperature to stay above (dew point + 1 °C margin).

Indoor dew point and minimum roof deck temperature: Indoor humidity to dew point and minimum deck temperature
Indoor RH at 20 °CDew point (°C)Dew point (°F)Minimum deck temperature (°C)
30%2353
40%6437
50%94910
55%115112
60%125413
65%135614
70%145815
80%166217

Warm roof vs cold roof

Warm flat roof Cold flat roof Pitched roof, insulated at ceiling
Insulation Above the deck Between joists, below deck On the ceiling
Deck temperature Close to indoor Close to outdoor Close to outdoor
Condensation risk Low with a vapour control layer High: needs ventilation and vapour barrier Moderate: ventilate the loft

Flat roof dew point calculation, step by step

  1. Indoor dew point at 20 °C and 55% RH: 10.7 °C.
  2. Total R for a warm roof with R 4.0 insulation: 0.10 + 0.06 + 0.14 + 4.0 + 0.01 + 0.04 = 4.35 m²K/W.
  3. With −5 °C outside, the 25 °C drop splits by R. The deck top sits at about 20 − 25 × 0.30 ÷ 4.35 = 18.3 °C, well above the dew point.
  4. The membrane is near outdoor temperature, but indoor air can’t reach it through an intact vapour control layer.

Limits of this check

The calculation is steady state, like the first stage of an EN ISO 13788 assessment. It doesn’t include night sky cooling, rain, or moisture built in during construction, and it assumes the vapour control layer is continuous.

Roof insulation and minimum R above the deck

Indoor RH at 20 °C Dew point Deck must stay above
35% 4.1 °C 5 °C (with 1 °C margin)
40% 6.0 °C 7 °C (with 1 °C margin)
50% 9.3 °C 10 °C (with 1 °C margin)
55% 10.7 °C 12 °C (with 1 °C margin)
60% 12.0 °C 13 °C (with 1 °C margin)
70% 14.4 °C 15 °C (with 1 °C margin)

Roof condensation problems and fixes

Problem Likely cause Fix
Dripping from ceiling in cold snaps Air leaks into a cold roof Seal ceiling penetrations, add vapour control
Wet insulation under membrane Missing or torn vapour control layer Repair VCL, dry or replace insulation
Frost on loft side of sheathing Moist air in loft, poor ventilation Clear eaves vents, seal hatch
Dew on top of membrane Night sky cooling Normal; dries in the morning

Dew point calculator roof FAQs

How do you calculate the dew point in a roof assembly?

Find the indoor dew point, then calculate the temperature at each layer from its share of the total R-value. Any layer colder than the dew point could collect condensation if indoor air reached it.

Where should the dew point be in a flat roof?

In a warm flat roof it should sit within or above the insulation, with an airtight vapour control layer below the insulation so the deck stays warm and dry.

Why do cold flat roofs get condensation?

The deck sits on the cold side of the insulation. Moist indoor air leaking through the ceiling condenses on its underside, so cold roofs need a vapour barrier and good ventilation, and many codes now discourage them.

Does a warm roof need a vapour barrier?

Yes. A vapour control layer on the deck, under the insulation, stops indoor moisture reaching the cold membrane side.

How much insulation goes above the deck?

Enough that the deck stays above the indoor dew point at winter design conditions. Roofing designers check this with a dew point calculation, as the NRCA recommends.

Can condensation form on the outside of a roof?

Yes. On clear nights the membrane radiates heat to the sky and can drop several degrees below air temperature, so dew or frost forms on top.

What causes loft condensation?

Warm moist air leaking through hatches, downlights and pipe gaps, combined with blocked eaves ventilation.

What is the formula for deck temperature in a warm roof?

The formula is T deck = Tin − (Tin − Tout) × R below the deck ÷ total R; in a warm roof the insulation sits above the deck, so R below the deck is small.

How much insulation keeps a warm roof deck above the dew point?

R 4.0 m²K/W above the deck keeps the deck above 18 °C (64 °F) with 20 °C inside and −5 °C (23 °F) outside, well above a 10.7 °C indoor dew point.

Why is the inside surface resistance 0.10 for roofs?

The inside surface resistance is 0.10 m²K/W for roofs: upward heat flow moves air faster at a ceiling than at a wall (0.13).