Dew point calculator roof
Choose your roof type, set indoor and outdoor conditions and the insulation R-value. The calculator shows the temperature through every layer, the deck temperature and whether moist indoor air would condense anywhere in the roof.
Check your roof for condensation
Move a slider or type a value. Results and the chart update as you go.
How dew point calculator roof works?
To find the dew point in a roof, the calculator builds the layers for a warm flat roof, cold flat roof or pitched roof, shares the temperature drop by R-value and compares each layer with the indoor dew point. Warm roofs keep the deck above the dew point; cold roofs don't.
- It calculates the indoor dew point from room temperature and humidity.
- It builds the layers for your roof type: a warm flat roof has insulation above the deck; a cold flat roof and a loft have it at ceiling level.
- It shares the indoor-to-outdoor temperature drop across the layers in proportion to their R-values, using the upward heat-flow surface resistance of 0.10 m²K/W inside.
- It flags the first layer colder than the indoor dew point. That's where moist air leaking into the roof would condense.
Dew point calculator roof formula
Layer temperatures follow Tx = Tin − (Tin − Tout) × ΣR to x ÷ ΣR total, with an inside surface resistance of 0.10 m²K/W for upward heat flow and 0.04 m²K/W outside. The deck is safe when T deck > Td indoor.
- Td indoor dew point, °C
- ΣR total thermal resistance, m²K/W
- U 1 ÷ ΣR, W/m²K
- T deck deck temperature, °C
Dew point calculator roof conversion chart
Indoor dew point at 20 °C (68 °F) for common humidity levels, and the deck temperature to stay above (dew point + 1 °C margin).
| Indoor RH at 20 °C | Dew point (°C) | Dew point (°F) | Minimum deck temperature (°C) |
|---|---|---|---|
| 30% | 2 | 35 | 3 |
| 40% | 6 | 43 | 7 |
| 50% | 9 | 49 | 10 |
| 55% | 11 | 51 | 12 |
| 60% | 12 | 54 | 13 |
| 65% | 13 | 56 | 14 |
| 70% | 14 | 58 | 15 |
| 80% | 16 | 62 | 17 |
Warm roof vs cold roof
| Warm flat roof | Cold flat roof | Pitched roof, insulated at ceiling | |
|---|---|---|---|
| Insulation | Above the deck | Between joists, below deck | On the ceiling |
| Deck temperature | Close to indoor | Close to outdoor | Close to outdoor |
| Condensation risk | Low with a vapour control layer | High: needs ventilation and vapour barrier | Moderate: ventilate the loft |
Flat roof dew point calculation, step by step
- Indoor dew point at 20 °C and 55% RH: 10.7 °C.
- Total R for a warm roof with R 4.0 insulation: 0.10 + 0.06 + 0.14 + 4.0 + 0.01 + 0.04 = 4.35 m²K/W.
- With −5 °C outside, the 25 °C drop splits by R. The deck top sits at about 20 − 25 × 0.30 ÷ 4.35 = 18.3 °C, well above the dew point.
- The membrane is near outdoor temperature, but indoor air can’t reach it through an intact vapour control layer.
Limits of this check
The calculation is steady state, like the first stage of an EN ISO 13788 assessment. It doesn’t include night sky cooling, rain, or moisture built in during construction, and it assumes the vapour control layer is continuous.
Roof insulation and minimum R above the deck
| Indoor RH at 20 °C | Dew point | Deck must stay above |
|---|---|---|
| 35% | 4.1 °C | 5 °C (with 1 °C margin) |
| 40% | 6.0 °C | 7 °C (with 1 °C margin) |
| 50% | 9.3 °C | 10 °C (with 1 °C margin) |
| 55% | 10.7 °C | 12 °C (with 1 °C margin) |
| 60% | 12.0 °C | 13 °C (with 1 °C margin) |
| 70% | 14.4 °C | 15 °C (with 1 °C margin) |
Roof condensation problems and fixes
| Problem | Likely cause | Fix |
|---|---|---|
| Dripping from ceiling in cold snaps | Air leaks into a cold roof | Seal ceiling penetrations, add vapour control |
| Wet insulation under membrane | Missing or torn vapour control layer | Repair VCL, dry or replace insulation |
| Frost on loft side of sheathing | Moist air in loft, poor ventilation | Clear eaves vents, seal hatch |
| Dew on top of membrane | Night sky cooling | Normal; dries in the morning |
Dew point calculator roof FAQs
How do you calculate the dew point in a roof assembly?
Find the indoor dew point, then calculate the temperature at each layer from its share of the total R-value. Any layer colder than the dew point could collect condensation if indoor air reached it.
Where should the dew point be in a flat roof?
In a warm flat roof it should sit within or above the insulation, with an airtight vapour control layer below the insulation so the deck stays warm and dry.
Why do cold flat roofs get condensation?
The deck sits on the cold side of the insulation. Moist indoor air leaking through the ceiling condenses on its underside, so cold roofs need a vapour barrier and good ventilation, and many codes now discourage them.
Does a warm roof need a vapour barrier?
Yes. A vapour control layer on the deck, under the insulation, stops indoor moisture reaching the cold membrane side.
How much insulation goes above the deck?
Enough that the deck stays above the indoor dew point at winter design conditions. Roofing designers check this with a dew point calculation, as the NRCA recommends.
Can condensation form on the outside of a roof?
Yes. On clear nights the membrane radiates heat to the sky and can drop several degrees below air temperature, so dew or frost forms on top.
What causes loft condensation?
Warm moist air leaking through hatches, downlights and pipe gaps, combined with blocked eaves ventilation.
What is the formula for deck temperature in a warm roof?
The formula is T deck = Tin − (Tin − Tout) × R below the deck ÷ total R; in a warm roof the insulation sits above the deck, so R below the deck is small.
How much insulation keeps a warm roof deck above the dew point?
R 4.0 m²K/W above the deck keeps the deck above 18 °C (64 °F) with 20 °C inside and −5 °C (23 °F) outside, well above a 10.7 °C indoor dew point.
Why is the inside surface resistance 0.10 for roofs?
The inside surface resistance is 0.10 m²K/W for roofs: upward heat flow moves air faster at a ceiling than at a wall (0.13).