Dew point calculator wall assembly

Model a typical wall build-up and see the temperature at every layer. The calculator compares each layer with the indoor dew point, flags the first layer that's too cold, and gives the total R-value and U-value.

Check your wall for condensation

Move a slider or type a value. Results and the chart update as you go.

°C
%
°C
m²K/W

How dew point calculator wall assembly works?

To find the dew point in a wall assembly, the calculator works out the indoor dew point, then shares the indoor-to-outdoor temperature drop across each layer in proportion to its thermal resistance (R-value). The first layer colder than the dew point is where condensation would form.

  1. It calculates the indoor dew point from indoor temperature and relative humidity.
  2. It adds up the R-values of each layer, from the inside air film to the outside air film.
  3. The temperature drop across each layer is proportional to its share of the total R-value, so it plots the temperature at every interface.
  4. Where an interface is colder than the indoor dew point, warm moist air leaking that far would condense. That's the condensation plane.

Dew point calculator wall assembly formula

Each layer temperature follows Tx = Tin − (Tin − Tout) × ΣR to x ÷ ΣR total. R = thickness ÷ conductivity (λ), and the U-value is U = 1 ÷ ΣR in W/m²K. This is the first step of the Glaser method in EN ISO 13788.

Dew point calculator wall assembly conversion chart

Any surface inside the wall colder than this temperature will collect condensation if indoor air reaches it.

Indoor dew point by temperature and humidity: Indoor dew point (°C) by room temperature and relative humidity
Room temp30% RH40% RH50% RH60% RH70% RH
16 °C−1.62.45.68.210.5
18 °C0.24.27.410.112.5
20 °C1.96.09.312.014.4
22 °C3.67.811.113.916.3
24 °C5.49.612.915.818.2

Typical R-values of wall layers

R = thickness (m) ÷ conductivity λ (W/mK). Add the surface resistances (0.13 inside, 0.04 outside for horizontal heat flow) to the layer values to get the total R; U = 1 ÷ R.

Keeping the dew point out of your wall

Two strategies work: keep moist indoor air out of the wall (airtight inner layer and a vapour control layer where needed), or keep the first condensing surface warm (exterior insulation). The best walls do both and can dry to at least one side.

Limits of a dew point check

A steady-state check uses one indoor and one outdoor temperature. Real walls cycle every day, store moisture in timber and masonry, and get wet from rain. Use this check to compare options and spot obvious risks, and move to EN ISO 13788 (Glaser) or WUFI for design sign-off.

Insulation position compared

Strategy Sheathing temperature Condensation risk Notes
Cavity insulation only Cold Higher Needs airtight interior and vapour control
Exterior insulation only Warm Low Thermal bridges reduced too
Cavity + exterior (hybrid) Warm if ratio is right Low Follow code minimum ratios
Internal insulation on masonry Masonry cold Higher Use vapour-open, capillary-active systems

Insulation materials

Material λ (W/mK) R per 100 mm Vapour
Mineral wool 0.035–0.040 2.5–2.9 Open
EPS 0.032–0.038 2.6–3.1 Medium
PIR / polyiso 0.022–0.026 3.8–4.5 Closed (foil-faced)
Wood fibre 0.038–0.045 2.2–2.6 Open, hygroscopic
XPS 0.030–0.035 2.9–3.3 Low

Dew point calculator wall assembly FAQs

How do you calculate the dew point in a wall?

Calculate the indoor dew point from room temperature and humidity. Then share the indoor-to-outdoor temperature drop across the layers in proportion to their R-values. Any layer colder than the dew point is a potential condensation plane.

Where should the dew point be in a wall?

Ideally inside a layer that indoor air can't reach, such as within exterior insulation, or outside the structure altogether. The sheathing should stay above the indoor dew point.

Does exterior insulation prevent condensation?

Yes, if it's thick enough. Exterior insulation keeps the sheathing warm. Building codes such as the IRC give minimum ratios of exterior to cavity insulation by climate zone for this reason.

Do I need a vapour barrier?

Yes, in most cold climates, on the warm side. In hot-humid climates a vapour barrier can trap moisture. Airtightness matters more than vapour diffusion in most walls.

Is a dew point calculation enough to check a wall?

No. It's a useful first check (the Glaser method in EN ISO 13788). Hygrothermal simulation such as WUFI models drying, rain and moisture storage, and is needed for high-risk assemblies.

What is the U-value of a wall?

The rate of heat loss: U = 1 ÷ total R in W/m²K. Lower is better. New UK walls typically need about 0.18–0.26 W/m²K.

What indoor humidity should I use?

Use winter design values: often 20 °C and 50% RH for homes, higher for pools, kitchens and bathrooms.

Why does air leakage matter more than vapour diffusion?

Air leaking through a gap can carry 10–100 times more moisture than diffusion through the same area of plasterboard.

What is the formula for temperature inside a wall?

The formula is Tx = Tin − (Tin − Tout) × R to layer x ÷ total R, which shares the temperature drop by thermal resistance.

What U-value does R 3.0 give?

A total R-value of 3.0 m²K/W gives a U-value of 0.33 W/m²K (about R-17 in US units).

Which standard covers condensation in walls?

EN ISO 13788 covers surface and interstitial condensation in building components; ASHRAE Standard 160 covers moisture design criteria.